MIL-HDBK-1133
1
APPENDIX D (Continued)
Table D-1 (Continued)
3
4160GndY/2400X12,470GndY/7200
208Y/120
25
149
430
3
4160GndY/2400X12,470GndY/7200
208Y/120
37.5
198
585
3
4160GndY/2400X12,470GndY/7200
208Y/120
45
223
683
3
4160GndY/2400X12,470GndY/7200
208Y/120
150
560
1690
3
4160GndY/2400X12,470GndY/7200
208Y/120
225
880
2420
3
4160GndY/2400X12,470GndY/7200
208Y/120
300
1050
3250
3
4160GndY/2400X12,470GndY/7200
208Y/120
500
1600
5200
3
4160GndY/2400X12,470GndY/7200
208Y/120
750
1800
8400
3
4160GndY/2400X12,470GndY/7200
208Y/120
1000
2100
10400
3
4160GndY/2400X12,470GndY/7200
208Y/120
1500
2900
16500
3
4160GndY/2400X12,470GndY/7200
480Y/277
75
360
990
3
4160GndY/2400X12,470GndY/7200
480Y/277
112
530
1270
3
4160GndY/2400X12,470GndY/7200
480Y/277
150
560
1690
3
4160GndY/2400X12,470GndY/7200
480Y/277
225
800
2500
3
4160GndY/2400X12,470GndY/7200
480Y/277
300
1050
3050
3
4160GndY/2400X12,470GndY/7200
480Y/277
500
1600
4900
3
4160GndY/2400X12,470GndY/7200
480Y/277
750
1800
7600
3
4160GndY/2400X12,470GndY/7200
480Y/277
1000
2100
8800
3
4160GndY/2400X12,470GndY/7200
480Y/277
1500
3300
13200
3
4160GndY/2400X12,470GndY/7200
480Y/277
2500
4800
21800
3
4160GndY/2400X12,470GndY/7200
480Y/277
3750
6500
29000
3
12,470GndY/7200
208Y/120
75
360
990
3
12,470GndY/7200
208Y/120
112
530
1270
3
12,470GndY/7200
208Y/120
150
560
1690
3
12,470GndY/7200
208Y/120
225
880
2420
3
12,470GndY/7200
208Y/120
300
1050
3250
3
12,470GndY/7200
208Y/120
500
1600
5200
3
12,470GndY/7200
208Y/120
750
1800
8400
3
12,470GndY/7200
208Y/120
1000
2100
10400
3
12,470GndY/7200
208Y/120
1500
2900
16500
3
12,470GndY/7200
480Y/277
75
360
990
3
12,470GndY/7200
480Y/277
112
530
1270
3
12,470GndY/7200
480Y/277
150
560
1690
3
12,470GndY/7200
480Y/277
225
880
2420
1
Although this table has value related to losses for older
existing transformers, it is not accurate for transformers
that the Navy has been procuring through NAVFAC guide
specifications such as NFGS-16272. The no load losses derived
from the NFGS are lower than those in this table. The load
losses for larger transformers derived from the NFGS are lower
than those in this table.
58