UFC 3-420-01
25 October 2004
403.1.4 Other users. When persons other than employees are permitted the
use of toilet facilities on the premises, the number of fixtures will be appropriately
increased according to 403.3 when determining the minimum number required.
403.2
UOPH & UEPH. Plumbing fixture allowances for Unaccompanied
Officers Personnel Housing (UOPH) will be according to Table 403-3. Plumbing
fixture requirements for Unaccompanied Enlisted Personnel Housing (UEPH) will
be as follows. A central bathroom will be provided for E1 Recruits. Fixture
allowances are provided in Table 403-4. For Grade E1 to E4 provide a two-
person shared bathroom and for Grade E5 to E6 provide a private bathroom.
Bathrooms will contain a lavatory with base cabinet, water closet, and a shower
or combination tub/shower unit.
Table 403-3. FIXTURE ALLOWANCES FOR UOPH
Occupant
Fixtures
WI to 06
Bathroom for each suite will
provide one lavatory, one water
closet, and one bathtub with
shower. Each floor will include
one drinking fountain
Table 403-4. FIXTURE ALLOWANCES FOR UEPH
(Minimum number of persons per fixture)
Water
Drinking
Occupants
Closets
Showers
Lavatories
Fountains
751
E1 Recruits
5
3
5
1
An additional drinking fountain will be provided in recruit housing for every 30 occupants per floor above
the initial 75 occupants requirement.
403.3 Other occupancies. Plumbing fixture allowances for religious, welfare
and recreational facilities for persons other than employees, where separate
toilet facilities are provided, will be according to Table 403-5.
A-6