UFC 3-420-01
25 October 2004
Table 606.5.11-1. TANK FILL PUMPS
Location
Number of
Gpm (L/s)
Min. Pump
Fixtures
per Fixture
Capacity (L/s)
Administration
1-25
1.23
(0.08)
25
(1.5)
Building
26-50
0.9
(0.06)
35
(2.2)
51-100
0.7
(0.045)
50
(3.2)
101-150
0.65
(0.04)
75
(4.7)
151-250
0.55
(0.03)
100
(6.3)
251-500
0.45
(0.03)
140
(7.8)
501-750
0.35
(0.02)
230
(15.0)
751-1000
0.3
(0.02)
270
(17.0)
1000-up
0.275
(0.02)
310
(20.0)
Apartments
1-25
0.6
(0.04)
10
(0.6)
26-50
0.5
(0.03)
15
(0.9)
51-100
0.35
(0.02)
30
(1.9)
101-200
0.3
(0.02)
40
(2.5)
201-400
0.28
(0.02)
65
(4.1)
401-800
0.25
(0.015)
120
(7.6)
801-up
0.24
(0.015)
210
(13.0)
Hospitals
1-50
1.0
(0.06)
25
(1.6)
51-100
0.8
(0.05)
55
(3.5)
101-200
0.6
(0.04)
85
(5.4)
201-400
0.5
(0.03)
135
(7.9)
401-up
0.4
(0.025)
210
(13.0)
Industrial
1-25
1.5
(0.10)
25
(1.6)
Buildings
26-50
1.0
(0.06)
40
(2.5)
51-100
0.75
(0.05)
60
(3.8)
101-150
0.7
(0.045)
80
(5.0)
151-250
0.65
(0.04)
110
(7.0)
251-up
0.6
(0.04)
165
(10.5)
1-50
0.65
(0.04)
25
(1.6)
And Barracks
51-100
0.55
(0.03)
35
(2.2)
101-200
0.45
(0.03)
60
(3.8)
201-400
0.35 ( 0.20)
100
(6.3)
401-800
0.275 (0.02)
150
(9.5)
801-1200
0.25 (0.015)
225
(14.5)
1200-up
0.2
(0.01)
300
(19.0)
Schools
1-10
1.5
(0.09)
10
(0.06)
11-25
1.0
(0.06)
15
(0.9)
26-50
0.8
(0.05)
30
(1.9)
51-100
0.6
(0.04)
45
(2.8)
101-200
0.5
(0.03)
65
(4.1)
201-up
0.4
(0.025)
110
(7.0)
A-19