UFC 3-600-01
17 April 2003
with change 16 January 2004
4-8.1
Application.
Installation of new
Halon 1301 systems is
prohibited
except by special approval of the AHJ in the component office listed in paragraph
1-4.6.
4-9
PORTABLE FIRE EXTINGUISHERS. Portable fire extinguishers
must be provided where required by NFPA 101, Life Safety Code. Portable fire
extinguishers must be located and installed in accordance with NFPA 10,
Portable Fire Extinguishers.
Exception: For Industrial and Storage occupancies, provide and
install extinguishers in accordance with NFPA 10.
4-9.1
Extinguisher Cabinets.
Recessed or
semi-recessed enclosed
cabinets must be provided in new or renovated facilities, except storage and
industrial occupancies.
4-10
WET CHEMICAL EXTINGUISHING SYSTEMS.
4-10.1
Application. Fixed wet chemical systems are suitable for
protection of certain types of special occupancies, hazards, and facilities, such as
cooking surfaces, cooking exhaust systems, and dip tanks.
4-10.2
Design Requirements. Wet chemical systems must conform to
NFPA 17A, Wet Chemical Extinguishing Systems.
4-11
CLEAN AGENT FIRE EXTINGUISHING SYSTEMS.
4-11.1
Application. Clean agent fire extinguishing systems are suitable
for protection of certain types of special occupancies, hazards, and facilities.
Clean agent fire extinguishing systems are not a substitute for required automatic
sprinkler systems.
4-11.2
Design Requirements. Clean agent fire extinguishing systems
must conform to NFPA 2001, Clean Agent Fire Extinguishing Systems.
4-12
WATER MIST FIRE PROTECTION SYSTEMS.
4-12.1
Application. Water mist fire protection systems are suitable for
protection of certain types of special occupancies, hazards, and facilities. Water
mist fire protection systems are not a substitute for required automatic sprinkler
systems.
4-12.2
Design Requirements. Water mist fire protection systems must
conform to NFPA 750, Standard on Water Mist Fire Protection Systems.
31