UFC 3-600-01
17 April 2003
with change 16 January 2004
moderate, stockpiles of combustibles do not exceed 2.5 m (8 ft), and fires with
moderate rates of heat release are expected. Modest, scattered amounts of
flammable liquid, in closed containers are allowable in quantities not to exceed
75 L (20 gal) per fire area. This classification includes but is not limited to the
following occupancies:
Armories
Sheet metal shops
Bowling alleys
Ship fitting shops
Clubs (officer, enlisted personnel, etc.)
Kitchens and bakery
Small stores
Theaters and auditoriums
Welding shops
Forge shops
Laundries
Automobile parking garage
Electronics assembly and repair
B-1.3
Ordinary Hazard Group 2 Occupancies. Occupancies or portion
of occupancies where quantity and combustibility of contents is moderate,
stockpiles do not exceed 3.7 m (12 ft), and fires with moderate rate of heat
release are expected. Moderate, scattered amounts of flammable liquids in
closed containers are allowable in quantities not to exceed 200 L (50 gal) per fire
area. Small amounts of flammable liquids may be exposed as required by
normal operations. This classification includes but is not limited to the following
occupancies:
Exchanges
Aviation Depots
Boiler rooms
B-87