UFC 4-010-01
8 October 2003
injuries or fatalities in adjacent structures. The separation distance is predicated on the
potential use of indirect fire weapons.
D-1.2.1
Billeting and Primary Gathering Structures.
D-1.2.1.1
Container Structures and Pre-engineered Buildings. For these
structures, apply the guidance in Appendix B.
D-1.2.1.2
Fabric Covered and other Expeditionary or Temporary Structures.
For all new billeting and primary gathering structures, ensure that adjacent structures
are separated by at least the distances in Table D-1. Where it is necessary to encroach
on those structure separations, analyze the structure and provide hardened structure
components as necessary to mitigate the effects of the explosive indicated in Table D-1
to the appropriate level of protection as shown in Table D-1. Levels of protection are
described in Table 2-2 and in the DoD Security Engineering Planning Manual.
D-1.2.2
Other Inhabited Structures. There are no minimum separation
distances required for antiterrorism for inhabited buildings other than billeting and
primary gathering structures.
D-1.3
Standard 3. Unobstructed Space. Keep areas within 10 meters (33
feet) of all expeditionary and temporary structures free of items other than those that are
part of the utilities and other supporting infrastructure.
D-2
ADDITIONAL STANDARDS. In addition to the specific standards
detailed in this appendix, apply the standards from Appendix B to expeditionary and
temporary structures as follows:
D-2.1
Fabric Covered and other Expeditionary or Temporary Structures.
Apply the following standards from Appendix B to these structures:
D-2.1.1
Standard 3. Drive-Up/Drop Off Areas.
D-2.1.2
Standard 4. Access Roads.
D-2.1.3
Standard 10. Windows and Glazed Doors.
D-2.1.4
Standard 11. Building Entrance Layout.
D-2.1.5
Standard 20. Equipment Bracing.
D-2.1.6
Standard 22. Mass Notification.
D-2.2
Container Structures and Pre-engineered Buildings. For these
structures, all standards in Appendix B apply.
D-3
ANTITERRORISM RECOMMENDATIONS. Apply all recommendations
except for Recommendation 7 (Access control for family housing) and Recommendation
8 (Standoff for family housing) from Appendix C to all expeditionary and temporary
structures.
D-3