UFC 4-133-01N
24 February 2005
Design facilities in accordance with UFC 4-010-01, DoD Minimum Antiterrorism
Standards For Buildings.
2-5.9
Electrical Requirements.
2-5.9.1
Emergency Electrical Power.
Provide an emergency generator with automatic starting and switching capability
as described in Paragraph 3-5.2. Consider a common generator when the ATCT
is sited adjacent to the air operations building, RATCF, FACSFAC, and JCF.
Provide emergency power to:
a. All loads as required by NFPA-101.
b. Electronic equipment in the tower cab and electronic equipment
rooms.
c.
Building mechanical systems supporting electronic equipment.
d. Exterior security lighting and security systems.
2-5.9.2
Uninterrupted Power Supply (UPS).
Provide non-redundant UPS in accordance with Paragraph 3-5.2.3. Use
anticipated load to determine the size of UPS.
2-5.10
Lighting.
Design lighting in accordance with HB-9-00. Provide dimmer adjustable white
ceiling lights in tower cab. Provide down lighting over work areas on separate
dimmer adjustable switch for each operator position.
2-5.11
Fire Protection.
See UFC 3-600-01, Design: Fire Protection Engineering for Facilities, and NFPA
101, Life Safety.
2-5.12
Security.
ATCTs are normally located within restricted areas that meet the minimum-
security measures for external security. If the facility is located within a restricted
area of a lower level of security, provide additional measures to meet the
minimum-security requirements for the level of security assigned to the facility.
The level of security and the designer's responsibility for particular security
elements will be designated in the IDSEP. See Paragraph 3-6. Provide an
electronic cipher door lock at the first floor entrance with an intercom and remote
lock release in the tower cab. The door at the stairs leading to the cab also
requires a cipher lock. See FRD.
24