UFC 4-133-01N
24 February 2005
c.
Provide overlapping light distribution to minimize reductions in
d. Protect all components of the system from vandalism.
e. Provide lights on buildings.
f.
Provide an emergency power generator within the security area.
Provide emergency power source adequate to sustain protective
lighting of all critical areas and structures for 8 hr. Provide
generator- or battery-powered lights at key control points in case a
failure disables the secondary power supply.
g. Install special-purpose lighting (such as fog penetration) when
climatic or other local factors dictate.
h. Provide additional lighting for (CCTV) security surveillance, as
necessary.
3-7.2.2
Intrusion Detective Systems (IDS).
Provide IDS when required by the level of security assigned to the facility. See
NAVFAC DM-13.02, Commercial Intrusion Detection Systems (IDS). The IDSEP
or user command will provide specific IDS requirements.
3-7.2.3
CCTV.
Provide CCTV when required to supplement security guard personnel, assist in
threat assessment and surveillance. See MIL-HDBK-1013/1.
3-7.3
Interior Physical Security.
3-7.3.1
Delay Times.
Guidelines for selecting and designing facility components to meet specified
delay times are provided in MIL-HDBK-1013/1. Procedures for determining delay
times, if not specified by the IDSEP or the user command, are given in MIL-
HDBK-1013/1.
3-7.3.2
Building Layout.
Portions of the building requiring special security consideration will be identified
by the IDSEP or by the user command.
3-7.3.3
Wall Construction.
Design secure area wall using 102 mm (4 in.) of reinforced concrete or 204 mm
(8 in.) of solid masonry, without windows, and with controlled access. See DCID
33