MIL-HDBK-1028/3
SUPERSEDES PART
O F DD-1291743
NOTES
P L U M B I N G REQUIREMENTS
65 G.P.M.
C O L D WATER
H O T WATER
R E C O V E R Y RATE
6 0 G.P.H.
( T H R U 100 RISE)
70 GAL.
STORAGE
T H E ABOVE RATES DO NOT INCLUDE
REQUIREMENTS FOR FIRE PROTECTION
H E A T I N G REQUIREMENTS (M BTU/HR)
70" F
INSIDE DESIGN TEMPERATURE
O U T S I D E DESIGN TEMPERATURE
+15 F
+25 F
+5 F
-5 F
432
302
367
504
A I R CONDITIONING REQUIREMENTS
S H O P SPACES
MIN. 70 F.D.B.
I N S I D E DESIGN T E M P E R A T U R E
MAX. 40 F.D.B.
4 0 % R.H.
I N S I D E DESIGN H U M I D I T Y
P E R S O N N E L SPACES
78 F.D.B.
I N S I D E DESIGN T E M P E R A T U R E
5 0 % R.H.
I N S I D E DESIGN H U M I D I T Y
492
C O O L I N G LOAD (M BTU.HR)
E L E C T R I C A L REQUIREMENTS (KW)
LIGHTS
72.0
C O N N E C T E D LOAD
57.6
E S T I M A T E D DEMAND
POWER
41.8
C O N N E C T E D LOAD
33.4
E S T I M A T E D DEMAND
TOTAL
113.8
C O N N E C T E D LOAD
91.0
E S T I M A T E D DEMAND
A D D I T I O N A L DEMAND FOR AIRCONDITIONING
41.0
AREAS
G R O S S AREA INCLUDING MECHANICAL
7 , 1 9 2 S.F.
E Q U I P M E N T ROOM
1 , 5 5 0 S.F.
VEHICLE SHED
DATE F A C I L I T Y PLATE NO SHEET
TITLE
SEP
5
AIR/UNDERWATER
WEAPONS
SHOP
216-55
86
OF 8
26