MIL-HDBK-1032/2
3.11.2
and explosion-proof fixtures with guards for hazardous materials storage
areas. Comply with requirements of NFPA 30 and NFPA 70.
3.11.3
Receptacles. Locate convenience outlets at least every 10 feet
(3050 mm) along wall space in offices and every 50 feet (15 240 mm) in all
other areas.
3.11.4
Battery Chargers. Provide circuits to power battery chargers for
battery-operated materials handling equipment.
Emergency Lighting. Provide a battery-powered emergency lighting
3.11.5
system to provide exit and storage aisle lighting.
Plumbing Requirements. Provide plumbing fixtures and capacity in
3.12
accordance with NAVFAC DM-3.01, DOD 4270.1-M, and the following:
3.12.1
Cold Water. Nominal flow rate for cold water, exclusive of fire
protection requirements, shall be 55 gallons per minute (3.5 liters per
second).
3.12.2
Hot Water. Provide a minimum of 30 gallons (115 liters [L]) of hot
water storage capacity. Provide additional capacity for facilities requiring
washdown operations.
Floor Drains. Provide floor drains with drain traps for general
3.12.3
purpose and cold storage areas. A single floor drain may serve more than one
area. When it is anticipated that a floor drain trap may lose its water seal
because of infrequent use, means for automatically maintaining the seal shall
be provided. Automatic priming of the trap may be through a drain from a
fixture within the area or by a connection to the water system. When
automatic priming is through a device connected to the water system, that
device shall be equipped with a vacuum breaker. Floor drains are not
72