MIL-HDBK-1032/2
Section 7: SHED STORAGE
Definition. Sheds are permanent structures without complete sides
7.1
and end walls. Utilities such as water, electric, and natural gas, may be
provided depending upon personnel support and fire protection requirements.
Sheds are used for the storage of material that requires maximum ventilation
or material that does not require complete protection from the weather.
Section 7 provides additional specific criteria applicable to shed storage.
7.1.1
General Purpose Shed. Provide minimum utilities consisting of
electricity for lighting and electrically operated equipment and tools.
Provide fire protection in proportion to the type of material stored and the
loss potential.
Transitory Shed. Transitory sheds are prefabricated structures
7.1.2
which can be dismantled for movement and reassembly. They can also be
positioned on concrete slabs.
Flammable/Hazardous Materials Shed. Bottled gases and drummed POL
7.1.3
materials shall be stored in sheds specifically designed for such
occupancies. Provide roof ventilators and ceiling sprinkler systems.
Separate bottled gas storage from drummed POL storage with a 4-hour fire
wall. Provide spill containment as described in subparagraph 7.3.2.
7.2
General Requirements. Design sheds for general purpose storage
unless specific applications are designated in the design process.
7.2.1
Layout. Refer to NAVFAC P-272, drawings 1404519 and 1404520, for
typical shed configurations. Shed layout shall be determined by function and
site conditions.
7.2.1.1
Shape and Proportion. Shed shape and proportion shall be dictated
by storage requirements and site conditions. Sheds for bottled gas and
drummed POL storage -shall not exceed a 3:l ratio of length to width. Sheds
designed for vehicle or other storage may be elongated. Length shall be
limited to 600 feet (183 m).
7.2.1.2
Access. Provide access from all sides in an open POL shed or only
Evaluate access requirements on the basis of function and site location.
7.2.2
Support Areas. Support functions for shed storage shall be provided
by adjacent covered storage facilities. When such facilities are not
available, provide office and rest room areas within the immediate shed
storage area.
7.2.2.1
Supervisory Offices. Supervisory offices shall be located in
existing covered storage facilities and provide the most efficient adjacency
relationship with the shed storage areas, employee service and operating
areas, parking, and utilities.