Cooler and condenser coils should be sprayed with a commercial
grade liquid cleaner or detergent, flushed with water, and dried with
compressed air. Outdoor cooling towers and evaporative condensers, including
piping, should be flushed, drained, and adequately protected with paint or
other corrosion preventive coating; piping should be disconnected at
equipment.
Coils and traps should be valved off and drained. Humidifying
systems should be shut off and flushed, cleaned, and drained. Humidifying
pads or filtering elements not suitable for further use should be discarded;
usable pads and filters should be removed, cleaned, wrapped, and packed in
suitable containers. Pneumatic control systems, including compression
equipment, should be drained of water deposits and blown dry with compressed
air.
Mechanical Ventilating Systems. Surfaces of equipment and bearings
2.2.7.6
should be protected to inhibit corrosion. Blower shafts should be greased
with heavy cup grease, and all bearings should be oiled. Driving pulleys and
fan belts should be removed and fastened to driven pulleys.
Heating, Ventilating and Air Conditioning (HVAC) Systems
2.2.8
General.
2.2.8.1
Inspect heating and air conditioning systems and test
them for proper operation. Remove all sealing devices from ducts and filters;
check for blockage caused by any accumulation of dust and dirt. Check all
electrical and plumbing connections. Remove shrouding and preservation
material and compounds and ready equipment for return to service. All piping
should be checked for leaks and repaired as necessary.
Air Conditioning Systems. Replace stored refrigerant or add new
2.2.8.2
refrigerant in all refrigeration equipment. Remove all closures on outside
exhaust and intake openings and louvers, on air supply grills, and on ducts to
buildings. Release blocked fans. Replace all fan motors, belts, pumps,
usable pads, and filters that have been stored. Inspect and adjust belts.
Suitable filtering or softening material should be replaced in filters and in
water-softening equipment in accordance with the manufacturer's
recommendations. Stored, usable humidifying pads or filtering elements should
be cleaned and installed.
Mechanical Ventilating Systems. Remove heavy grease from blower
2.2.8.3
operation and adjust drive belt tension.
Automatic Control Equipment and Meters. Meters and instruments
2.2.8.4
removed from their mountings should be re-installed on automatic control
equipment.
Pipe connections from controls to heating equipment should be
reconnected, flushed, and filled. All containers for water, ink, or acid on