4-19. ARTS AND CRAFTS/SKILL DEVELOPMENT CENTERS. These facilities may be air
conditioned provided the functions require ventilation rates beyond that based on the number of
occupants only (such as metal and woodworking shops) or where excessive heat releases are
generated by equipment housed in the facility (such as kilns and welding equipment).
4-20. OTHER ELIGIBILITY CRITERIA.
a. Provide air conditioning for the following facilities only in locations where the dry bulb
temperature is 26.66 degrees C (80 degrees F) or higher for over 650 hours or the wet bulb
temperature is 19.44 degrees C (67 degrees F) or higher for over 800 hours during the six
warmest months of the year:
(1) Auditoriums and Theatres.
(2) Banks.
(3) Bowling Alleys.
(4) Chapels.
(5) Daycare Centers, Schools, and Libraries.
(6) Stores and Exchanges.
(7) Clubs and Dining Facilities.
(8) Post Offices.
(9) Indoor Target Ranges.
b. The following types of facilities are not eligible for air conditioning regardless of weather
conditions:
(1) Boiler Plants.
(2) Greenhouses.
18