90
3.10.3.4.4 Consider providing power for video projector and
including public address system with a microphone in any large
conference room.
3.10.3.4.5 Provide multioutlet raceway, based on Tenant
requirements, with receptacles in photo lab, NOC/IT, armorers'
3.10.3.4.6 Provide a minimum of 4 receptacles in reproduction
rooms.
copy machines and special office equipment. Verify whether Tenants
have any equipment with special electrical requirements
3.10.3.4.8 Provide empty conduit system for intrusion detection
system (IDS) in arms vaults and AGCCS. Provide power supply for
the Government-provided IDS controller.
3.10.3.4.9 Receptacles located in hazardous areas of maintenance
shop workbays should be mounted at a minimum of 460 mm above
finished floor.
3.10.3.4.10 A security light outside the arms vaults should be
provided.
3.10.4 Communications
3.10.4.1 A/E should determine the local telephone service provider in
the area. A/E should record the company name, address, contact
person, telephone number, e-mail address, and any discussions
concerning service, requirements and costs. A/E should furnish a
preliminary site plan with proposed telephone service conduit routing
and estimated number of telephone instruments to the telephone
company or local base.
3.10.4.2 Underground telephone service conduit, 103 mm diameter
should be installed from the main telephone terminal board to the
property line. Telephone service cable normally furnished and installed
by the local telephone utility company.
3.10.4.3 Verify service needs for telephone switch with the Tenants;
AR preference is for utility-provided switching, either remote or
through a leased on-site switch. If Using Service approves an AR
Installation-purchased switch, verify switch specifications and
construction contract include it with collateral equipment.
||content||
\