MIL-HDBK-1164
Table 35 (Continued)
Inspection
Action
(1), (2)
Chains
Drain off water, add oil as necessary.
M
Change oil.
SA
Annular ball
Lubricate.
D
bearings
Inspect condition.
M
See manufacturer's instructions.
V
bushings, etc.
Tank equipment
Tighten bolts and nuts. Check for
A
excessive wear. Flush and backblow
and shear pins. Check rakes. Clean
and paint equipment.
Conveyor-type-collector
See above, and consult manufacturer's
V
basins
instructions.
Upflow or solids-contact
See manufacturer's instructions.
V
clarifier
(1) D-Daily; W-Weekly; Q-Quarterly; SA-Semiannually; A-Annually;
V-Variable, as conditions may indicate.
(2) The frequencies shown are suggested frequencies that may be modified by local
command, as individual installation conditions warrant.
(3) Caution: Do not allow cross-connections to the drinking
water supply system.
11.5.4.2
Lubrication Requirements. Regular lubrication is required when the basin
is in continuous operation. Intermittent operation may allow an increase in the
lubrication interval. If operating periods are intermittent and infrequent, operate the
mechanism briefly between operating periods and lubricate accordingly. Devices
subject to wide seasonal temperature variations will require seasonal changes in
lubricant grades, especially when summer grade oils thicken at lower temperatures and
reduce the flow capability. Daily or weekly lubrication of operating units is part of the
operator's inspection. The choice of lubricant and its frequency of application are
175