UFC 3-300-10N
25 May 2005
2-3.3.9 Provide anchors and ties for cavity walls. Do not use corrugated metal ties or
ties with an integral drip in cavity walls.
2-3.3.10 Horizontal joint reinforcing may be used in conjunction with reinforcing bars to
meet minimum prescriptive reinforcing requirements in lightly loaded walls. Joint
reinforcing must not be considered to resist computed stresses.
2-3.4
Structural Steel.
2-3.4.1 Unless otherwise noted herein, all structural steel design and construction
must be in accordance with UFC 1-200-01.
2-3.4.2 Refer to FEMA 350, FEMA 351, FEMA 352, FEMA 353, FEMA 355, and 2002
AISC Seismic Provisions for Structural Steel Buildings for additional seismic design
guidance for structural steel buildings.
2-3.4.3 Structural steel fabrication and erection procedures must be in accordance
with AISC Code of Standard Practice.
2-3.4.4 Structural steel framing systems must be designed for vibration serviceability
due to human activity in accordance with AISC Steel Design Guide Number 11.
2-3.4.5
Preferred material selections are as follows:
ASTM A992 for W shapes
ASTM A36 for M, S, HP, C, MC, and L sections
ASTM A53 for steel pipe
ASTM A500 for HSS sections
ASTM A36 for plates and bars
ASTM A108 for headed shear studs
ASTM F1554 for anchor rods
ASTM A325 for bolts
ASTM F959 for Direct Tension Indicating washers (DTI's)
ASTM F1852 for twist off type tension control bolts
These materials shall be used to the maximum extent possible.
2-3.4.6 Any single panel point of the lower chord of exposed roof joists or trusses or
any point along the length of exposed primary structural members supporting roofs over
manufacturing, storage and warehousing, or maintenance shops must be capable of
safely supporting a suspended concentrated load of 8.90 kN (2000 pounds) in addition
to dead loads. For all other occupancies, a concentrated load of 0.89 kN (200 pounds)
must be used instead of 8.90 kN (2,000 pounds).
2-3.4.7 All structural steel exposed to the weather must adequately protected to
prevent corrosion. All galvanized structural steel shall in accordance with ASTM
A123/123M or ASTM A153/153M, as applicable. Galvanize after fabrication where
2-7