UFC 3-410-02N
8 June 2005
CHAPTER 1
INTRODUCTION
1-1
PURPOSE AND SCOPE. This UFC is comprised of two sections.
Chapter 1 introduces this UFC. Appendix A contains the full text copy of the previously
released Military Handbook (MIL-HDBK) 1003/3. This UFC serves as criteria until such
time as the full text UFC is developed from the MIL-HDBK and other sources.
This UFC provides general criteria for the design of passive solar
buildings.
1-2
APPLICABILITY. This UFC applies to all Navy service elements and
Navy contractors.
1-2.1
General Building Requirements. All DoD facilities must comply with
UFC 1-200-01, Design: General Building Requirements. If any conflict occurs between
this UFC and UFC 1-200-01, the requirements of UFC 1-200-01 take precedence.
1-2.2
Safety. All DoD facilities must comply with DODINST 6055.1 and
applicable Occupational Safety and Health Administration (OSHA) safety and health
standards.
NOTE: All NAVY projects, must comply with OPNAVINST 5100.23 (series), Navy
Occupational Safety and Health Program Manual. The most recent publication in this
series can be accessed at the NAVFAC Safety web site:
OPNAVINST 5100.23, the requirements of OPNAVINST 5100.23 take precedence.
1-2.3
Fire Protection. All DoD facilities must comply with UFC 3-600-01,
Design: Fire Protection Engineering for Facilities. If any conflict occurs between this
UFC and UFC 3-600-01, the requirements of UFC 3-600-01 take precedence.
1-2.4
Antiterrorism/Force Protection. All DoD facilities must comply with
UFC 4-010-01, Design: DoD Minimum Antiterrorism Standards for Buildings. If any
conflict occurs between this UFC and UFC 4-010-01, the requirements of UFC 4-010-01
take precedence.
1-2.5
Humid Area HVAC Design. Navy facilities must comply with the
requirements in ITG FY05-2, NAVFAC Humid Area HVAC Design Criteria.
1-3
REFERENCES.
UFC 1-200-01, Design: General Building Requirements, available at the
UFC 3-600-01, Design: Fire Protection Engineering for Facilities available
1-1