UFC 3-580-10
14 July 2004
Including changes 12 April 2005
TABLE C-2
NMCI MINIMUM LOADS*
OCCUPANCY UNIFORM UNIFORM CONCENTRATED CONCENTRATED
or USE
(kPa)
(psf)
(kN)
(lbs)
7.2
150
8.9
2000
Converted
Spaces for
Pops
3.6
75
4.45
1000
Converted
Spaces for
ERs
2.4
50
No
No
Converted
Recommendation
Recommendation
Spaces for
TRs
* Floors must be designed to support the uniformly distributed live loads or the
concentrated loads shown above, whichever produces the greater load effects.
Unless otherwise specified, the indicated concentration is assumed to be
uniformly distributed over a 0.76 by 0.76 m (2.5 by 2.5 ft) area (0.58m2 (6.25 ft2)
and located to produce the maximum load effects in the structural members.
43