UFC 3-600-01
17 April 2003
with change 16 January 2004
A minimum of 30.5 m (100 ft) from any flammable or combustible
liquids handling, servicing, processing, or storage area.
A minimum of 15.3 m (50 ft) from any buildings of Type III, IV, or V
construction.
A minimum of 7.6 m (25 ft) from any buildings of Type I or Type II
construction.
6-19.4
Bulk Tank Vehicle Parking. Design parking for bulk tank vehicles
servicing fixed tanks that meet the separation requirements of NFPA 50, for the
fixed bulk tank.
Exception: As modified in paragraph 6-19.3.
6-19.5
LOX Storage for Propellant Applications. Use liquid oxygen
storage for propellant applications that comply with 29 CFR 1910.109, Explosives
and Blasting Agents.
Exception: As modified in paragraph 6-19.3.
6-20
DEPARTMENT OF DEFENSE DEPENDENT SCHOOLS. These
facilities must comply with educational occupancies in NFPA 101.
6-21
VEHICLE PARKING, STORAGE, MAINTENANCE, AND REPAIR
FACILITIES. Design facilities utilized for the parking, storage, maintenance, and
repair of general and special purpose motor vehicles to comply with NFPA 88A,
Parking Structures and/or NFPA 88B, Repair Garages.
6-21.1
Vehicle Parking. Protect enclosed buildings used for vehicle
parking and storage of 10 or more vehicles with an automatic sprinkler system.
6-21.2
Overhaul and Repair Shops. Facilities falling within this category
are those in which major overhaul and repairs are made to various types of
equipment or their component parts. Disassembly and testing may also be
performed in such facilities, which include aircraft shops, automotive garages and
repair shops, and ship repair shops.
6-21.2.1
Requirements. Design automotive garages to conform to NFPA
88B. Design ship repair facilities to conform to NFPA 303, Marinas and
Boatyards, and NFPA 312. Design major aircraft overhaul and repair shops to
conform to paragraph 6-15.
6-21.3
Refueler Vehicle Facilities. Facilities used for the parking,
storage, maintenance, and repair of aircraft refueler vehicles should:
Be protected by an automatic sprinkler system or a closed-head
foam-water AFFF sprinkler system, and
58