UFC 3-600-01
17 April 2003
with change 16 January 2004
Table 6-1 (Navy and Air Force)
SEPARATION DISTANCE BETWEEN OUTDOOR INSULATED TRANSFORMERS
and BUILDINGS
Horizontal Distancea
Fire
Non-
Vertical
Resistant
Combustible Combustible
Liquid Volume Construction Construction Construction Distance
Liquid
gal (m)
ft (m)
ft (m)
ft (m)
ft (m)
Less
<1,000 (3.8)
5 (1.5)
5 (1.5)
25 (7.6)
25 (7.6)
Flammable
>1,000 (3.8)
15 (4.6)
15 (4.6)
50 (15.2)
50 (15.2)
<500 (1.9)
5 (1.5)
15 (4.6)
25 (7.6)
25 (7.6)
Mineral Oil
500 5,000
15 (4.6)
25 (7.6)
50 (15.2)
50 (15.2)
(1.9 19)
>5,000 (19)
25 (7.6)
50 (15.2)
100 (30.5)
100 (30.5)
a
If FM Approved transformers are used, the separation distances shall follow the
requirements of FM Global Loss Prevention Data Sheet 5-4, Transformers, which
allows for reduced separation distances.
Table 6-2 (Army)
SEPARATION DISTANCE BETWEEN OUTDOOR INSULATED TRANSFORMERS
and BUILDINGS
Horizontal Distancea
Fire
Non-
Vertical
Transformer
Resistant
Combustible Combustible
Construction Construction Construction Distance
Rating
Liquid
kVA
ft (m)
ft (m)
ft (m)
ft (m)
Less
<2000
5 (1.5)
5 (1.5)
25 (7.6)
25 (7.6)
Flammable
>2000
15 (4.6)
15 (4.6)
50 (15.2)
50 (15.2)
Mineral Oil
5 (1.5)
15 (4.6)
25 (7.6)
25 (7.6)
<1000
(transformers
made after 1970
except zigzag-
>1000
15 (4.6)
25 (7.6)
50 (15.2)
50 (15.2)
type)
<650
5 (1.5)
15 (4.6)
25 (7.6)
25 (7.6)
Mineral Oil
650 6500
15 (4.6)
25 (7.6)
50 (15.2)
50 (15.2)
(transformers
made before
1970 & zigzag-
>6500
25 (7.6)
50 (15.2)
100 (30.5)
100 (30.5)
type)
a
If FM Approved transformers are used, the separation distances shall follow the
requirements of FM Global Loss Prevention Data Sheet 5-4, Transformers, which
allows for reduced separation distances.
6-27.2.2.2.1.1
When the separation distance in Table 6-1 or Table 6-2
cannot be met, the following applies:
63