UFC 3-600-01
17 April 2003
with change 16 January 2004
Table 6-5
ELECTRIC TRACTION ELEVATOR
ROOM / AREA
PROVIDE
PROVIDE SMOKE DETECTOR
SPRINKLER
to INITIATE ELEVATOR
FIREFIGHTERS SERVICE and
(Not Applicable for
BUILDING FIRE ALARM
Buildings Without
SYSTEM
Sprinkler Protection)
PENTHOUSE
YES
YES
MACHINE ROOM
ELEVATOR LOBBIES
YES
YES
PIT AREA
NO
NO
TOP of HOISTWAY
NO *
NO *
* Provide sprinklers and smoke detector where existing hoistway walls are not 2
hour rated, and existing elevator cab does not meet flame spread or smoke
development requirements of ASME A 17.1. These sprinklers must follow the
requirements of paragraphs 6-29.4.3 and 6-29.5.