UFC 3-600-01
17 April 2003
with change 16 January 2004
Figure 6-10
Holeless Hydraulic Elevator
SD
Elevator
To Elevator Power
Cab
Elevator Lobby
Disconnect
To
Fire Alarm
SD
SD
Test
Machine Room
Elevator Lobby
No more than 24-inches
above the pit floor.
6-30
TENSION FABRIC STRUCTURES.
6-30.1
Separation of, and Basic Allowable Area. To determine the
allowable area and separation requirements for all permanent tension fabric
structures, follow the requirements of Table 6-8. The separation area will be a
clear zone adjacent to the tension fabric structure. The clear zone cannot be
used for storage and must be clear of vegetation (maintained lawn is permitted).
The clear zone may be used as a street or driveway, but not for vehicle parking.
6-30.2
Definitions:
6-30.2.1
Tension Membrane Structure (from NFPA 102): A membrane
structure incorporating a membrane and a structural support system such as
arches, columns, and cables, or beams wherein the stresses developed in the
tension membrane interact with those in the structural support so that the entire
assembly acts together to resist the applied loads.
6-30.2.2
Permanent Building (from NFPA 102): A building that is intended to
remain in place for a period of 180 days or more.
74