UFC 3-600-01
17 April 2003
with change 16 January 2004
6-34.1
Renovation. Renovation of existing building of Type III, Type IV
and Type V construction over 465 m2 (5,000 ft2) must include automatic sprinkler
protection.
6-35
MISSILE ALERT FACILITIES (MAF). MAFs are the aboveground
facilities that support underground ballistic missile launch control centers.
6-35.1
Sprinkler Protection. Protect all missile alert facilities with a
sprinkler system designed and installed in accordance with National Fire
Protection Association 13R, Standard for the Installation of Sprinkler Systems in
Residential Occupancies up to and Including Four Stories in Height. Systems
must be supplied from the existing domestic water storage tank. Use dry-
pendant or dry-sidewall heads or anti-freeze runs for rooms/spaces exposed to
freezing temperatures.
6-35.2
Heat Detectors.
Thermal detection devices must be
provided in
rooms, areas and spaces that are not protected by automatic sprinkler protection
in accordance with NFPA 13R.
6-35.3
Fire Hydrants. Provide a dry fire hydrant installed on the domestic
water tank to allow local fire departments the ability to draft firefighting water
during emergencies.
77