UFC 4-133-01N
24 February 2005
Provide non-redundant UPS with maintenance bypass switch in accordance with
Paragraph 3-5.2.3. Use anticipated load to determine the size of UPS.
2-4.5.2
Emergency Electrical Power.
Provide an emergency generator with automatic starting and switching capability
as described in Paragraph 3-5.2. Provide emergency power to:
a. All loads as required by NFPA-101.
b. Electronic equipment in operations, NTDS/ACDS, and equipment
rooms.
c.
Building mechanical systems supporting electronic equipment.
d. Exterior security lighting and security systems.
2-4.5.3
400-Hz Power.
Provide 400-Hz (Hz) power in accordance with Paragraph 3-5.2.4, when required
by the FRS
2-4.6
Lighting.
Design lighting in accordance with HB-9-00. Provide dimmer adjustable red or
blue lights in the IFR room. See SSCC FRD for additional information.
2-4.7
Security
The JCF is normally located within restricted areas that meet the minimum-
security measures for external security. If the facility is located within a restricted
area of a lower level of security or is located remote and outside of an
established restricted area, provide additional measures to meet the minimum-
security requirements for the level of security assigned to the facility. Security at
the main building entrance usually requires a single entry point with visitor
control. Remote locks, video cameras, card readers, and/or keypads may be
required by NISCOM as components of the IDS. The level of security and the
designer's responsibility for particular security elements will be designated in the
IDSEP. See Paragraph 3-6. Provide:
a. Electronic cipher door locks at all access points to operations room.
b. Exterior doors in operations, NTDS/ACDS system,
equipment/maintenance, and mechanical/electrical rooms with no
access hardware on the outside.
c.
Closed circuit TV (CCTV).
14