UFC 4-150-02
12 May 2003
Table 3-2 Shore Steam and Condensed Shore Steam Quality Requirements1 2
CONSTITUENT OR PROPERTY
REQUIREMENT
pH
8.0 to 9.5
25 [mu]S/cm maximum2
Dissolved Silica
0.2 ppm maximum
0.10 ppm max or 5 ppm as
Total Suspended Solids
0.10 ppm maximum
1.
Steam must be generated from feedwater which is either treated with a chemical
oxygen scavenger or mechanically deaerated to a maximum dissolved oxygen
content of 15 parts per billion. Shore steam and condensed shore steam used
as feedwater must meet the above standards. The use of filming amines is
prohibited.
2.
[mu]S/cm = micro-Siemens/centimeter = micro-mho/centimeter. The lowest
Table 3-3 Bulk Shore Feedwater Quality Requirements1
CONSTITUENT OR PROPERTY
REQUIREMENT
pH
5.4 to 8.2 (process effluent)
Conductivity
2.5 [mu]S/cm maximum (at point
of delivery2
Silica
0.2 ppm maximum
1.
Produced by method other than condensed steam.
2.
[mu]S/cm = micro-Siemens/centimeter = micro-mho/centimeter.