MIL-HDBK-1027/4A
TABLE 2.4 (Continued)
TRAINER FACILITIES DATA-F/A-18 OFT
STRUCTURAL
Device components transport method: Cockpit by casters and lifted by lifting
fixtures or fork lift truck.
Special equipment: Overhead track and hoist with 500 pound capacity.
Maximum concentrated computer access floor load: 47.8 pounds per square inch.
Max column floor pad load from trainee station: 18.0 pounds per square inch.
MECHANICAL
SPACE NAME
TEMPERATURE
HUMIDITY
EQUIP
DEGREES(f)
PERCENT
HEAT (BTU/HR)
_____________________________________________________________________________
Device/Trainee Area
60-80
40-60
103,400
Instructor/Operator
60-80
40-60
9600
Computer Room
60-80
40-60
111,390
Utility Area
40-100
50-80
51,360
ELECTRICAL
SPACE NAME
VOLTS
HZ
WIRE
PHASE LIGHT
COUNT
LEVEL
Device/Trainee Area
120
60
2+GND
50fc
Instructor/Operator
120
60
2+GND
75fc
Computer Room
120/208
60
4+GND
3
75fc
Utility Area
480Y/277
60
4+GND
3
50fc
General note: Electrical power furnished by the facility should be:
160 AMP, 120/208 VAC, three phase, 60 Hz, four wire plus ground
55 AMP, 480Y/277 VAC, three phase, 60 Hz, four wire plus ground
Grounding:
Earth Ground required.
50