MIL-HDBK-1027/1B
Provide a 40 mm fire water line to the deep fat fryer
fireplace and terminate it with a globe valve below floor
grating. The water should be used for APC extinguishing agent
simulation.
For propane usage, agent usage, and total utilities,
see Table 4.
Table 4
19F1A and 19F1B Structures
________________________________________________________________
FIRE
NO. OF
CLASS
TIME
FIRES
________________________________________________________________
A
Wednesday
AM
12 fires
PM
12 fires
B
Thursday
AM
12 fires
PM
12 fires
C
Friday
AM
12 fires
PM
12 fires
________________________________________________________________
PROPANE USAGE
________________________________________________________________
NO. OF
TOTAL
FIRES/
PROPANE PROPANE/
CLASS GROUP
PROPANE
USE PER GROUP
OF
(15 MEN)
DEMAND
FIRE
FOR 2 DAYS
FIRES
2 DAYS
FIRE TYPE
L/s
L
A
3
Trash Can
4.75
425
1274
3
Mattress/Locker 19.5
849
2547
3
Steam Clothes
Dryer
4.75
425
1275
3
Storage
Compartment
19.5
849
2547
3
Vent Duct
4.75
425
1274
B
4
Bilge/Oil
Spray (Note 1) 66
9905
39 620
4
Bilge (Note 2) 83
12 395
49 582
3
Deep Fat Fryer/
Fryer Hood
19.5
849
2547
86