MIL-HDBK-1027/1B
Table 13
19F5 and 19F5A Structures
________________________________________________________________
CLASS SCHEDULE
________________________________________________________________
A
Monday AM
240 fires
B
PM
240 fires
________________________________________________________________
Note: The 2-day course includes a classroom session before the
fire training.
________________________________________________________________
PROPANE USAGE
________________________________________________________________
TOTAL
PROPANE AVERAGE
PROPANE PROPANE/
CLASS NO. OF
DEMAND
FIRE
USE PER CLASS
OF
FIRES/
L/s
DURATION FIRE
FOR 1 DAY
FIRES CLASS FIRE TYPE
min
min
L
L
A
160
Trash Can
5
2
566
67 920
B
160
Bilge
31
2
4528
724 480
C
160
Electric
2
2
283
33 960
Panel 480
826 360/
fires/class
class
________________________________________________________________
Notes: 1. Each fireplace should have 10 fires/hour.
2. Maximum fires per shift is 480 fires. Classes
larger than 160 students can be accommodated by
reducing student fire exposure or extending the
shift.
3. Great Lakes should train additional students with
the same number of fires.
4. The propane demand is based on a gas pressure at the
burner of 7 kPa except for the bilge fire which is
14 kPa.
5. The design propane demand for the structure is
(5 + 31 + 2) x 2 = 76 L/s.
124