MIL-HDBK-1028/1C
b) In the ancillary spaces, automatic wet-pipe
sprinkler system should be provided.
c) Provide manual and automatic fire alarm system
reporting to the base-wide system.
3.8
Environmental. Design should be in accordance with
follows:
3.8.1
Floor Drains and Waste Disposal System. Design for
accidental spill of paint strippers and thinners, paint,
Provide for zero discharge from the facility unless the facility
will discharge to an existing or new industrial waste treatment
facility (IWTF) or to a municipal sewer system. In each case,
the IWTF must be capable of handling both the type and volume of
the chemicals that will be discharged. Consult the EFD or EFA
Environmental Branch for appropriate discharge standards.
Provide above-grade containment of accidental spills with
appropriate sumps for pumping and cleanup of spilled wastes.
Size the containment capacity for the largest possible
discharge. Provide a method to ensure that the drains are
prevented from clogging.
3.8.2
Volatile Organic Compounds (VOC). Every effort should
be made to achieve compliance by use of compliant coatings vice
use of VOC emission controls.
38