MIL-HDBK-1028/3
d) Equipment and wiring in the paint shop shall be in accordance
with NFPA 33.
5.6.2
The lighting requirements of para. 2.4.2 are applicable
Lighting.
to this facility.
5.6.3
Emergency Power. An emergency diesel electric generator shall be
provided, with capacity as required by the using agency to meet the essential
loads of the facility.
5.6.4
Shielding. An electromagnetic radiation survey shall be conducted
to determine if shop spaces require shielding. Shielding for Shop No. 1 and
Shop No. 2 shall be provided when a requirement is established by the survey.
Refer to NAVSEA 0P-3565.
5.6.5
Grounding and Lightning Protection. Grounding requirements of
para. 2.4.3, are applicable to this facility. Lightning protection shall be
provided in accordance with NAVFAC DM-4.06, Lightning (and Cathodic)
Protection, and NAVSEA OP-5.
5.6.6
between the duty office and the guard house, shop areas, instrument testing,
and garage.
5.7
Security. Security features shall be provided in accordance with
mandatory requirements which must be obtained from NAVFACENGCOM HQ. Selected
light fixtures and the alarm control center shall be connected to the
5.8
Explosion-Proof Weight-Handling Equipment. The overhead bridge
crane in the torpedo storage room shall have electric motorized bridge,
trolley, and hoist with 3,000-lb, (1,360 kg) capacity. The monorail hoist in
Shop No. 1 and No. 2 shall have electric motorized trolley and hoist with
2,000-lb (907 kg) capacity. The monorail hoist in the paint shop shall be a
hand-operated hoist and trolley with 1,000-lb. (453 kg) capacity. Electric
bridge, trolley, and hoist motors shall be operated from floor level by push
button pendent controls and shall be capable of operating at slow speeds for
positioning loads and at higher speeds for moving loads. Classification of
hazardous locations shall be as defined in NFPA 70 (refer to NAVFAC DM-38.01
for additional criteria).
17