UFC 4-390-01
23 July 2003
c)
d)
e)
Fit up and inspection results
f)
Welding procedure number
g)
h)
Welder or brazier number
i)
Type of inspection and results
j)
Disposition of joint (pass/fail)
k)
Any repairs of joint
l)
Inspection procedure number
m)
NDT inspection number
n)
Signature and date
B.4.3.3 NDT Records. Copies of all nondestructive testing (NDT)
records should be provided. Qualification records of
nondestructive test personnel should be maintained and provided
to the SCA.
B.4.3.4 Dye Penetrant (PT) Inspection. Records of dye penetrant
inspections should be maintained and should consist of:
a)
Type(s) of dye penetrant tests
b)
Identification of assembly, part, etc.,
c)
Number of cracks
d)
Type(s) of cracks
e)
Signature and date of the assigned responsible
individual verifying all specified PT inspection including
PT of any required repairs has been accomplished and is
satisfactory
B.4.3.5 Radiographic (RT) Inspection. Chambers are required to
have full radiographic testing (RT) of all pressure retaining
butt welds (joint efficiency of 1). Records of radiographic weld
inspection should contain, as a minimum, the following:
a)
Date of exposure of the radiograph
b)
Positively identified location of weld radiographed
69