UFC 4-390-01
23 July 2003
c)
Type of material and material thickness
d)
Type of weld joint
e)
Approved procedure identification
f)
Energy source (isotope type, intensity, kilo-voltage
and focal spot size of x-ray machine)
g)
Type of film, screens, source-to-film distance, and
exposure time
h)
Penetrameter designation
i)
Image Quality Indicator (IQI) sensitivity reading
j)
Applicable acceptance standards
k)
Flaws (unacceptable slag, porosity, or other
indications)
l)
Acceptance or rejection
m)
Date of interpretation and signature of film
interpreter(s)
n)
Interpreter's documented qualification level should be
noted
o)
Diagram (radiograph map) indicating the specific
location of each radiograph coded to its unique number
Where required by contract, a copy of the actual radiographs
should be provided to the government.
B.4.3.6 Ultrasonic (UT) Inspection. Records of ultrasonic
inspection should contain, as a minimum, the following:
a)
Date of the ultrasonic inspection
b)
Description and unique item identification, weld
location and joint identification
c)
Type of material and material thickness
d)
Type of weld joint and length of weld inspected
e)
Approved procedure identification
f)
Equipment used for inspection (instrument and search
unit): manufacturer and model number, transducer size and
type, search beam angle, test frequency, couplant
g)
70