MIL-HDBK-1164
Table 26
Maintenance Checklist for Fire Hydrants
Inspection
Action
Dry-barrel
Check drain valve to be sure it opens.
A
hydrants
Where ground water level rises into barrel,
A
plug drain valve and dewater barrel by a
pump.
Wet-barrel
Check packing glands and valve seats;
A
hydrants
repair as necessary.
Pit-type hydrants
Check for water accumulation; dewater as
A
necessary.
All hydrants
On dead ends
Flush; check barrel after flushing.
A
Flush; check barrel after flushing.
A
Not on dead
ends
Check water flow.
A
Repair as necessary; if main shut down is
V
required, notify fire department.
In winter
Check for freezing; thaw if necessary.
W (3)
M (4)
Leakage tests
Inspect all places where leaks might occur;
A
repair as necessary.
Valve parts
Operating
Check for rounded corners; replace as
A
nut
necessary; lubricate.
Nozzle threads
Check for damage; replace as necessary.
A
Chains
Check for paint fouling; clean.
A
Flow tests
Determine hydrant flow.
A
(1) W-Weekly; M-Monthly; A-Annually; V-Variable, as conditions may indicate.
(2) The frequencies shown are suggested frequencies that may be modified by local
command, as individual installation conditions warrant.
(3) Weekly near important structures.
(4) Monthly elsewhere.
142