MIL-HDBK-1164
Table 47 (Continued)
Inspection
Action
(1), (2)
SA
Steel tanks
If problem is noted during inspection,
(standpipes)
arrange for an outside contractor to repair
the steel tank.
Steel tanks
Check tank interior, roof, and
SA
(underground storage)
appurtenances.
Steel tanks (elevated
If problem is noted during inspection,
SA
storage)
arrange for an outside contractor to repair
the steel tank.
Tanks
Use contractor.
SA
Tower
Check for corrosion and for loose, missing,
SA
structures
bowed, bent, or broken members; loose
sway bracing; misalignment of tower legs;
or evidence of instability. Repair as
necessary.
Roofs
Check obstruction and navigation lights,
SA
hoods, shields, receptacle, and fittings for
missing or damaged parts or inoperation;
cables, and ground connections; repair,
replace, or renew; paint as necessary.
Risers and heating
Two months before freezing weather,
A
systems
check riser pipe insulation and repair as
necessary; also check heating system
operation.
One month before freezing weather,
A
operate heating system for 8 hours; repair
or adjust defective parts.
230