MIL-HDBK-1011/2
APPENDIX C (continued)
Pick predominant wind direction associated with the 82deg.F to 86deg.F band
for the
month. (This range roughly corresponds to conditions when ventilation is
effective.
(b) OPTION 2: If no SMOS exists for the location, use RUSSWO Part
C--"Surface Winds." Pick predominant wind direction for month.
WS = ))))) knts = ))))) knts
(6)
Wind speed for month, WS.
From SMOS or RUSSWO Part C--"Surface
Winds", pick mean windspeed corresponding
to direction chosen in Step 5 for the month.
a = ))))) deg = ))))) deg
(7)
Incidence angle on windward face,
alpha, from site plan and prevailing
wind direction, (see Figure C-2).
(8)
From Table C-1 or C-2 determine:
WPC = )))) = )))))
LPC = )))) = )))))
PCD = )))) = )))))
(9)
Pressure coefficient differential, PCD.
PCD = WPC - LPC
(10)
For the surrounding
PCCF = )))) = )))))
neighborhood and the proposed
building type, determine from
Table C-3 the pressure coefficient
correction factor, PCCF.
PD = )))) = )))))
(11)
Calculate the revised pressure
coefficient differential, PD.
PD = PCD x PCCF
TCF = )))) = )))))
(12)
Obtain terrain correction
factor, TCF, from Table C-4.
W = )))) fpm = )))) fpm
(13)
Compute revised meteorological wind
speed in feet per minute, W.
W = WS x TCF x 101.2
A = ))))) ft.2-= )))) ft.2-
(14)
Calculate required open effective
window area, A.
A = (1.56 CFM) / [W x (PD)1/2]
Select an open inlet area, A+i, > A. A+i,= ))))) ft.2-= )))) ft.2-
(15)
Note: if equal inlet and outlet
area are desired, A+i, =1.41A.