Table 1 (Continued)
Factors for Individual Facilities by Navy Category Code1
DEMAND LOAD
NAVY
FACTOR FACTOR
CODE
Description
(%)
(%)
226
Plating maintenance . . . . . . . . . .
.
.
.
.
.
.
.35-40
18-23
226
Mixing . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.40-45
18-23
226
Segregation fleet return . . . . . . .
.
.
.
.
.
.
.35-40
15-20
226
Plaster load . . . . . . . . . . . . .
.
.
.
.
.
.
.35-40
15-20
Fluoroscope building . . . . . . . . .
.
.
.
.
.
.
.45-50
18-23
Tank building rocket . . . . . . . . .
.
.
.
.
.
.
.40-45
15-20
.
.
.
.
.
.
.35-40
15-20
Phosphorous loading . . . . . . . . . .
.
.
.
.
.
.
.35-40
15-20
226
Vacuum and hydraulic pump building . .
.
.
.
.
.
.
.35-40
12-17
226
Cable drive . . . . . . . . . . . . . .
.
.
.
.
.
.
.35-40
12-17
226
Dryer building . . . . . . . . . . . .
.
.
.
.
.
.
.75-80
3- 8
Miscellaneous Production Facilities:
229 50
Printing plant . . . . . . . . . . . .
. . . . . . .45-55
25-30
Miscellaneous Storage Facilities:
750
Community Facilities - morale, welfare,
and
recreation - exterior . . . . . . . .
. . . . . . .Determine by
load count
and time.
750 30
Outdoor swimming pool installation . . . . . . . . .80-85
20-25
750 54
Band stand . . . . . . . . . . . . . . . . . . . . .75-80
15-25
Miscellaneous Facilities for Utilities and Ground
Improvements:
821 09
Heating plant building (condensate) . . . . . . . . .55-60
25-40
821 09
Heating plant building (heating) . . . . . . . . . .55-60
30-35
833 40
Garbage house . . . . . . . . . . . . . . . . . . . .75-80
20-25
841
load count
and time.
845 20
Pipeline nonpotable water . . . . . . . . . . . . . .55-60
3- 8
852 30
Pedestrian bridge . . . . . . . . . . . . . . . . . .80-85
20-25
872 20
Guard and watch towers . . . . . . . . . . . . . . .80-..
46-..
890 20
Compressed air plant . . . . . . . . . . . . . . . .60-65
20-25
1Demand factors include allowance for system loss.