Table 1 (Continued)
Factors for Individual Facilities by Navy Category Code[1]
DEMAND
LOAD
NAVY
FACTOR FACTOR
CODE
DESCRIPTION
(%)
(%)
217
10
.35-40
20-25
218
20
Construction/weight handling equipment shop . . . .
.35-45
20-25
218
40
Railroad equipment shop . . . . . . . . . . . . . .
.35-45
15-20
218
50
Battery shop . . . . . . . . . . . . . . . . . . .
.55-65
20-25
219
10
Public works shop . . . . . . . . . . . . . . . . .
.32-38
18-22
221
10
Aircraft engine assembly plant . . . . . . . . . .
.32-38
20-25
222
10
Missile assembly buildings . . . . . . . . . . . .
.35-40
15-20
222
20
Missile handling launch equipment . . . . . . . . .
.35-40
15-20
223
10
Fabrication/assembly building . . . . . . . . . . .
.22-27
24-29
225
10
Small arms plant . . . . . . . . . . . . . . . . .
.15-20
22-27
225
20
Light gun (20mm/51n) plant . . . . . . . . . . . .
.15-20
22-27
225
30
Heavy gun (6/161n) plant . . . . . . . . . . . . .
.16-21
21-26
225
50
Launcher/projector plant . . . . . . . . . . . . .
.15-20
22-27
226
10
Bag charge filling plant . . . . . . . . . . . . .
.62-67
23-28
226
15
Case filling plant . . . . . . . . . . . . . . . .
.35-40
23-28
226
20
Case overhaul tank repair facility . . . . . . . .
.35-40
18-22
226
35
Major-caliber projectile loading plant . . . . . .
.35-40
18-22
226
40
Medium-caliber projectile loading plant . . . . . .
.35-40
18-22
226
55
Cast high explosives filling plant . . . . . . . .
.35-40
18-22
226
65
Propellant and related chemical facility . . . . .
.30-40
32-38
227
10
Radio and radar equipment plant . . . . . . . . . .
.50-55
23-28
227
10
Sonar equipment plant . . . . . . . . . . . . . . .
.50-55
23-28
228
10
Parachute/survival equipment plant . . . . . . . .
.35-40
20-25
229
10
Asphalt plant . . . . . . . . . . . . . . . . . . .
.75-80
7-12
229
20
Concrete batching plant . . . . . . . . . . . . . .
.75-80
15-20
229
30
Rock crusher plant . . . . . . . . . . . . . . . .
.75-80
15-20
229
40
Sawmill . . . . . . . . . . . . . . . . . . . . . .
.45-55
15-20
300
Research, Development, Test & Evaluation Facilities:
310
13
Chemistry and Toxicology Laboratory . . . . . . . .
.70-80
22-28
310
15
Materials Laboratory . . . . . . . . . . . . . . .
.30-35
27-32
310
19
Physics Laboratory . . . . . . . . . . . . . . . .
.70-80
22-28
316
10
Ammunition, explosives, and toxics laboratory . . .
.28-32
20-25
317
20
Electrical and electronics systems laboratory . . .
.20-30
3-7
400
Supply Facilities:
421
Ammunition storage installation . . . . . . . . . .
.75-80
.....
423
Ammunition storage-liquid propellant . . . . . . .
.75-80
20-25
431
10
Cold storage warehouse . . . . . . . . . . . . . .
.70-75
20-25
441
10
General warehouse Navy . . . . . . . . . . . . . .
.75-80
23-28
441
20
Controlled humidity warehouse . . . . . . . . . . .
.60-65
33-38
441
30
Hazardous/flammable storehouse . . . . . . . . . .
.75-80
20-25
441
40
Underground storage . . . . . . . . . . . . . . . .
.65-70
23-28
441
70
Disposal, salvage, scrap building . . . . . . . . .
.35-40
25-20
1Demand factors include allowance for system loss.