UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Table 2-1 NMCI POP Facilities
Description**
Cabinets
Nominal Size *
3.72 m2 (40.0 ft2)
Small Site (non-redundant) 5
1
to 16 seats
3.72 m2 (40.0 ft2)
Small Site (redundant) 5 to
1
16 seats
3.72 m2 (40.0 ft2)
Small Base (non-redundant)
1
17 to 249 seats
5.57 m2 (60.0 ft2)
Small Base (redundant) 17 to
2
249 seats
5.57 m2 (60.0 ft2)
Medium Base (redundant)
2
250 to 450 seats
41.81 m2 (450.0 ft2)
9
Large Base (redundant); no
server farm 451 to 2000
seats
Notes: * Indicates minimum clearances, see paragraph 2-2.6 for
clarifications
** Redundant and non-redundant refer to inner and outer router in the
POP.
2-2.7
Structural. Equipment Room Structural Requirements are listed in
Appendix C.
2-2.8
Electrical. POP electrical requirements are dependent upon the
size of the POP. Table D-1 in Appendix D represents the NMCI electrical
requirements for each size POP. The ampacity at the service connection point
identified by the government for the TPP will be based upon the demand load of
the equipment. Figure D-1, Appendix D, represents a typical one line for the
POP equipment.
2-2.9
Grounding. Grounding requirements are listed in Appendix C.
2-2.10
Mechanical. Mechanical requirements are listed in Appendix C.
7