MIL-HDBK-1027/4A
TABLE 2.2 (Continued)
TRAINER FACILITIES DATA-F/A-18 WTT
ELECTRICAL
SPACE NAME
VOLTS
HZ
WIRE PHASE LIGHT ZONES
REMARKS
COUNT
LEVEL
Device/Trainee Area
120/208
60
4+GND
3
50fc
2
1,4
Instructor/Operator
120/208
60
4+GND
3
50fc
2
2,4
Debrief Station
120/208
60
4+GND
4
Computer Room (CIG)
120/208
60
4+GND
3
50fc
2
4
Computer Room (digital)
120/208
60
4+GND
3
50fc
4,5
Mechanical Pump Room.
120/208
60
4+GND
3
50fc
3,4
Maintenance Room.
120/208
60
4+GND
3
50fc
Maintenance Storage.
120/208
60
4+GND
15fc
Remarks:
1.
Primary zone should be on/off. Secondary zone includes Instructor
Station and should have dimmer.
2.
Included in Device Area zone. Locate controls for Device Area and
Instructor Station near the Instructor Station. Provide aimable &
dimmable lights over console work surface.
3.
Device contractor will step voltage up for 480 volt requirement.
4.
Conditioned power.
5.
Cable trenches and vertical cable raceways required between computer
rooms and training devices as noted.
General Notes:
Training Devices Connects: Device contractor supplies component wiring and
conduit from device to government disconnects or panel. Main power switch in
computer room.
Grounding:
Building, Equipment, and Signal Grounds required.
(if required)
40