MIL-HDBK-1027/1B
b)
c)
Foam nozzle
d)
Manual control valve
e)
f)
Controls
The foam reel is supplied with 6 percent foam from the
nearest FS type hose station.
4.9.5
Stand Pipe (SP).
A 65 mm stand pipe, supplied with
water.
a) A 65 mm hose angle valve with one end flanged and
the other end threaded, NAVSHIPS Dwg. 803-1385712.
b) A marine strainer and valve with connection
coupling on one end and a threaded connection on the other end
is no longer required.
c)
A 65 mm by (2) 40 mm wye gate.
4.9.6
Submarine Hose Station 1 (SHS1).
Hose station is
supplied with water and is wall mounted.
a) A 40 mm angle globe valve with one end flanged and
the other end threaded, NAVSHIPS Dwg. 803-1385712. The valve
should be located 457 mm above the floor next to the hose
station. The valve should be perpendicular to the wall and
should be served by piping routed in or through the wall.
b)
c) Wall mounted fire hose locker in accordance with
Appendix G, Figure G-8. The hose is rolled up and stored in the
locker.
d)
No strainer, wye gate, or applicator is required.
138