MIL-HDBK-1028/3
Lighting shall meet the following criteria:
Lighting.
2.4.2
a)
Interior lighting shall normally be fluorescent.
b)
Exterior lighting shall be high-pressure sodium vapor where
practical.
c) Design for lighting intensities shall be in accordance with
MIL-HDBK-1190, Facility Planning and Desire Guide.
d)
Fixtures and wiring in the paint shop shall be in accord with
NFPA 33.
Grounding and Liphtning Protection. Grounding and lighting
2.4.3
protection shall meet the following requirements:
a) Primary and secondary systems shall be provided (refer to
Chapter 4, Volume 1, NAVSEA OP-5).
b) Consider the use of cable reels for grounding conductors for
ordnance equipment in shop areas. Cable reels must be located so that they
do not interfere with overhead weight-handling equipment operations.
c) Grounding in the paint shop shall be in accord with NFPA 33.
Explosion-proof Weight-Handling Equipment. Monorail hoists and/or
2.5
bridge cranes shall be provided in main shop areas, when the size of the
ammunition units to be maintained are large enough to warrant weight-handling
equipment. Monorail hoists and bridge cranes shall be of sparkproof
construction with explosion- proof motors if electric powered. Controls
shall be operable from floor level and, when they are electric, shall be
explosion proof. Classification of hazardous locations shall be as defined
in NFPA 70. Refer to NAVFAC DM-38.01, Weight-Handling Equipment, for
additional criteria. Colors for weight-handling equipment shall be accord
with NAVFAC P-309, Color for Naval Shore Facilities.