MIL-HDBK-1028/3
as required to comply with pollution control requirements. Refer to
para.6-3.2.2, Volume 1, NAVSEA OP-5, for requirements concerning drainlines
handling explosive wastes. There shall be no drains from the paint spray
booths . Floor drains may be connected to the sanitary system in areas where
there is no Otto fuel present. There shall be no floor drains in the Otto
fuel areas or provide trench and sump system for spill control.
c) Plumbing for the battery charging area in compliance with Part
6, para. 7.c, DM-28.04.
3.3.4
Compressed Air. Compressed air shall be provided in accord with
Specifically provide:
NAVFAC DM-3.05.
a) low-pressure compressed air as described in para. 2.3.4, and
b) high-pressure compressed air at 3,000 psi (20,684 kPa) to main
shop areas of torpedo rework facilities. Dryers and filters shall be
specified to assure a clean and dry air supply.
3.3.5
Noise and Vibration Control. All mechanical systems and equipment
shall be designed to limit noise and vibration in accord with NAVFAC DM-3.10.
3.4
Electrical Requirements. Electrical requirements, including power
generation and distribution, lighting, grounding, and lightning protection
shall be in accord with Chapter 4, Volume 1 of NAVSEA OP-5; NFPA 70; NAVFAC
DM-4 Series; and the requirements defined in paras. 3.4.1 through 3.4.4,
shall also apply.
3.4.1
Power.
The following power requirements shall apply:
a) Single-phase, 120 Vat, 20 A, 60 Hz convenience outlets shall
be provided in all spaces with spacing as required by NFPA 70 and user
requirements.
b) Three-phase, 120/208 Vat, 60 Hz power outlets shall be
provided in main shop areas and instrument test rooms.
c) Three-phase, 115/200 Vat, 400 Hz and 28 Vdc power is required
for main shop areas and the instrument test room (refer to MIL-STD-704,
Aircraft Electric Power Characteristics, for 400 Hz and 28 Vdc requirements).
d) The ampacity of 3-phase and direct-current outlets shall be as
required by the using agency for the specific facility. Provide name plates
to indicate outlet characteristics.
e)
Equipment and wiring in the paint shop shall be in accord with
NFPA 33.
3.4.2
Lighting.
Lighting shall conform to the following criteria:
a) Interior lighting shall normally be fluorescent.
b) Exterior lighting shall be high-pressure sodium vapor where
practical.
8