UFC 4-721-10
31 July 2002
Interior and exterior lighting for the building,
Exterior site and parking area lighting,
Emergency lighting,
Telephone wiring,
Fire detection and annunciation,
Cable television wiring,
LAN Local Area Network system wiring for Computer hookup for
each occupant.
Intrusion detection systems at the exterior doors.
Provide metering for electric power.
For direct entrance rooms, provide three-way switches at the
entrance door and in the vanity area so that the living room and
bedroom area lighting is controlled at either location. Also, provide
motion sensor switches at bathroom doors to control the bathroom
light fixture.
Provide 20-ampere outlets throughout each Apartment/ Module/
Room per applicable electrical code. In bedrooms, provide 20
ampere dedicated quadraplex outlets combined with television and
telephone and computer data outlets as described. Provide
quadraplex and duplex outlets in the compact kitchen area.
Provide each Apartment/ Module/ Room with dedicated lines for
telephone, and data outlet (personal computers) and television of
each room occupant. Dedicate each line solely to a bedroom,
providing each bedroom with two combination outlets with duplex,
telephone, and data outlet and television for each occupant of each
room. Locate them on opposite walls to facilitate and coordinate
with the room furniture layout.
Ceiling Fans: Provide fans that are Energy Star compliant with pin-
based CFL. Do not use combination fan-light fixtures and ensure
that no strobe light effect is created by the fan/ light positioning.
Ceiling fans should be provided in renovation and new construction
for Navy projects. Ceiling fans are optional for the Marine Corps.
10-22