UFC 4-021-01
18 DECEMBER 2002
Figure 2-2. Use of Existing Public Address System
Fire Alarm
System
Temporarily
Deactivate Audible
Fire Alarm Appliances
Speakers As Needed
Existing Speakers
PA
New Speakers
Strobes
as Needed
Autonomous
Battery
Control
Backup
Existing Public Address System
Unit
Displays (Optional)
Notification
Appliance Network
Conductor Integrity Monitoring
Required
Local Operator Console
Individual Building System
2-4.2
Implementation of Giant Voice System. The Giant Voice system is typically
installed as a wide-area system to provide siren signal, pre-recorded, and live voice
messages. It is most useful for providing mass notification for personnel in outdoor
areas, expeditionary structures, and temporary buildings. Giant Voice is not usually
suitable for most permanent inhabited buildings, and must not be used in lieu of an
individual building mass notification system. If an optional base-wide control system for
mass notification is installed (see paragraph 2-5), it should be interfaced to a new or
existing Giant Voice system. Figure 2-3 shows the logical block diagram for a Giant
Voice system.