171
Figure 4-45 Battery Room and Toilet
4.5.9.5 Provide eyewash/deluge showers inside and outside the door
to the room.
4.5.9.6 Space Design Information
General/Code
Size varies
Occupancy high hazard storage
Occupancy count not occupied; typically 1 person per
27.9 sq m (300 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor sealed concrete
Base none
Walls painted CMU
Ceiling none, paint structure
Trim
Lockset storeroom
Mechanical
Cooling none
below 5% concentration; consider a hood above
batteries
Electrical
Lighting 20 fc; explosion-proof fluorescents on pilot-
lighted switch outside room
Voice/data none
Furniture Equipment
Battery shelving
UFC 4-171-05