UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Intermediate Cross Connect - Without Cooling Equipment(CONTINUED)
CABINET EQUIPMENT
VOLT
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
AMPS
SEAT CNTS
CABINET
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
BK AMP/POLE
Wire Size
Heat to Room
(Btu/hr)
SIDF27
<96
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
5,425
SIDF29
< 480
120/208/1 PH.
18
18
0
0
18
18
30/2
3#10, #10G, 3/4"C
13,125
SIDF31
< 336
120/208/1 PH.
15
15
0
0
15
15
30/2
3#10, #10G, 3/4"C
11,075
SIDF33
< 120
120/208/1 PH.
15
15
0
0
15
15
30/2
3#10, #10G, 3/4"C
11,075
SIDF35
<96
120/208/1 PH.
13
6
0
0
13
6
30/2
3#10, #10G, 3/4"C
7,401
SIDF41
< 24
120/208/1 PH.
20
10
0
0
20
10
30/2
3#10, #10G, 3/4"C
6,256
SIDF44
< 24
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
5,227
SIDF48
<48
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
5,227
WIDF10
< 24
120/208/1 PH.
5
3
0
0
5
3
30/2
3#10, #10G, 3/4"C
1,706
WIDF11
< 24
120/208/1 PH.
2
0
0
0
2
0
30/2
3#10, #10G, 3/4"C
829
WIDF14
< 24
120/208/1 PH.
2
0
0
0
2
0
30/2
3#10, #10G, 3/4"C
829
WIDF23
<7
120/208/1 PH.
2
0
0
0
2
0
30/2
3#10, #10G, 3/4"C
829
WIDF43
< 10LRE
120/208/1 PH.
2
0
0
0
2
0
30/2
3#10, #10G, 3/4"C
770
WIDF47
< 24
120/208/1 PH.
7
3
0
0
7
3
30/2
3#10, #10G, 3/4"C
2,526
WIDF54
< 24
120/208/1 PH.
6
0
0
0
6
0
30/2
3#10, #10G, 3/4"C
2,383
WIDF55
< 12
120/208/1 PH.
5
0
0
0
5
0
30/2
3#10, #10G, 3/4"C
1,849
66