UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Table D-3 Intermediate Cross-Connect
Intermediate Cross Connect - Without Cooling Equipment
CABINET EQUIPMENT
VOLT
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
AMPS
COOLING
SEAT CNTS
CABINET
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
AMP/POLE
Heat to Room
(Btu/hr)
CIDF18
<24
120/208/1 PH.
4
0
0
0
4
0
30/2
3#10, #10G, 3/4"C
1,361
CIDF19
< 72
120/208/1 PH.
16
0
0
0
16
0
30/2
3#10, #10G, 3/4"C
5,243
CIDF37
<12
120/208/1 PH.
4
0
0
0
4
0
30/2
3#10, #10G, 3/4"C
1,420
CIDF38
<36
120/208/1 PH.
10
21
0
0
10
21
30/2
3#10, #10G, 3/4"C
5,626
CIDF39
<18
120/208/1 PH.
20
21
0
0
20
21
30/2
3#10, #10G, 3/4"C
7,759
DBASEX1
N/A
120/208/1 PH.
13
12
0
0
13
12
30/2
3#10, #10G, 3/4"C
9,160
DBASEX2
N/A
120/208/1 PH.
7
5
0
0
7
5
30/2
3#10, #10G, 3/4"C
4,478
DIDF15
<192
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
3,728
DIDF20
< 72
120/208/1 PH.
6
10
0
0
6
10
30/2
3#10, #10G, 3/4"C
4,979
DIDF21
<24
120/208/1 PH.
12
8
0
0
12
8
30/2
3#10, #10G, 3/4"C
6,283
DIDF22
<24
120/208/1 PH.
4
5
0
0
4
5
30/2
3#10, #10G, 3/4"C
3,640
DIDF26
<192
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
5,425
DIDF28
<96
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
5,425
DIDF30
<72
120/208/1 PH.
17
17
0
0
17
17
30/2
3#10, #10G, 3/4"C
12,488
DIDF32
<96
120/208/1 PH.
15
15
0
0
15
15
30/2
3#10, #10G, 3/4"C
11,075
DIDF34
<144
120/208/1 PH.
16
9
0
0
16
9
30/2
3#10, #10G, 3/4"C
8,815
DIDF36
<96
120/208/1 PH.
10
7
0
0
10
7
30/2
3#10, #10G, 3/4"C
7,401
DIDF45
<24
120/208/1 PH.
7
7
0
0
7
7
30/2
3#10, #10G, 3/4"C
5,227
DIDF49
<48
120/208/1 PH.
1
1
0
0
1
1
30/2
3#10, #10G, 3/4"C
5,227
DIDF52
<24
120/208/1 PH.
10
5
0
0
10
5
30/2
3#10, #10G, 3/4"C
5,619