UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Main Cross Connect - With Cooling Equipment
VOLT
CABINET EQUIPMENT AMPS *
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
SEAT CNTS
CABINET
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A Phase B
BK AMP/POLE
Wire Size
Heat to Room
(Btu/hr)
DMDF1
< 96
120/208/1 PH.
23
21
10
10
33
31
60/2
3#6, #8G, 3/4"C
10,915
DMDF2
< 64
120/208/1 PH.
12
10
10
10
22
20
30/2
3#10, #10G, 3/4"C
7,197
DMDF3
< 64
120/208/1 PH.
11
9
10
10
21
19
30/2
3#10, #10G, 3/4"C
7,197
DMDF4
< 64
120/208/1 PH.
10
7
10
10
20
17
30/2
3#10, #10G, 3/4"C
6,331
DMDF5
< 60
120/208/1 PH.
10
8
10
10
20
18
30/2
3#10, #10G, 3/4"C
6,189
DMDF6
< 128
120/208/1 PH.
19
17
17
17
36
34
60/2
3#6, #8G, 3/4"C
13,848
DMDF6 (UPS Fault)
< 128
120/208/1 PH.
26
10
17
17
43
27
60/2
3#6, #8G, 3/4"C
13,848
DMDF7
< 64
120/208/1 PH.
25
22
(ECM)
(ECM)
25
22
40/2
3#8, #10G, 3/4"C
3,728 to ECM
DMDF7 (UPS Fault)
< 64
120/208/1 PH.
34
13
(ECM)
(ECM)
34
13
40/2
3#8, #10G, 3/4"C
3,644 to ECM
DMDF10
<128
120/208/1 PH.
16
14
20
20
36
34
60/2
3#6, #10G, 3/4"C
11,632
DMDF11
120/208/1 PH.
2
3
3
0
5
3
30/2
3#10, #10G, 3/4"C
2,258
DMDF12
120/208/1 PH.
8
6
10
10
18
16
30/2
3#10, #10G, 3/4"C
5,341
DMDF13
120/208/1 PH.
10
6
10
10
20
16
30/2
3#10, #10G, 3/4"C
6,753
DMDF14
120/208/1 PH.
16
14
20
20
36
34
60/2
3#6, #8G, 3/4"C
10,991
DMDF15
120/208/1 PH.
18
16
20
20
38
36
60/2
3#6, #8G, 3/4"C
12,408
SMDF9
<60
120/208/1 PH.
9
8
3
10
12
18
30/2
3#10, #10G, 3/4"C
6,192
* LOAD INCLUDES 1.5 AMPS FOR A CONVENIENCE OUTLET PER CABINET, WHICH IS NOT INDICATED ON CABINET ELEVATION SHEETS.
63