UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP 18- NON REDUNDANT SMALL BASE (SEATS 17-85) [Two 1-Ton A/C units]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
21
23
20
20
41
43
70/2
3#4, #8 G, 1"C
9,234
120/208/1 PH.
UPS FAILURE
33
12
20
20
53
32
DPOP 22- Non Redundant Small Base (17 To 85 Seats) [Two 1-Ton A/C unit ] EXT UPS
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
8,668
NORMAL
20
19
19
10
39
29
DPOP 1-Non-Redundant Small Site (1 to 16 Seats) [2 - 1 TON UNITS Preferred ]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
16
14
10
10
26
24
50/2
3#8, #10 G, 1"C
11,406
120/208/1 PH.
UPS FAILURE
33
12
10
10
43
22
58