UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP 24 & 25 Redundant Small Base -EXT. UPS-One -2 Ton A/C Alternate
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
12,602
NORMAL
8
8
17
17
25
25
DPOP4- Redundant Small Site (1 to 33 Seats) [Two 1-Ton A/C units - Preferred]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
17
10
20
20
37
30
70/2
3#4, #8 G, 1"C
10,196
120/208/1 PH.
UPS FAILURE
25
2
20
20
45
22
DPOP 4- Redundant Small Site (1 to 33 Seats) [One 2-Ton A/C unit Alternate]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
17
10
17
17
34
27
70/2
3#4, #8 G, 1"C
10,196
120/208/1 PH.
UPS FAILURE
25
2
17
17
42
19
56